The Totaline® P270-3000PL 4-wire photoelectric duct smoke detector features a pivoting housing that fits both square and rectangular footprints and mounts to round or rectangular ductwork. This unit senses smoke in the most challenging conditions, operating in airflow speeds of 100 to 4,000 feet per minute, temperatures of -4°F to 158°F, and a humidity range of 0 to 95 percent (non-condensing).

A plug-in sensor head offers improved false alarm immunity and simple installation, testing, and maintenance. An improved cover design isolates the sensor head from the low-flow feature for simple maintenance.
  • Photoelectric, integrated low-flow technology
  • Air velocity rating from 100'/min. to 4,000'/min. (0.5 m/s to 20.32 m/sec)
  • Versatile mounting options: square or rectangular configuration
  • Plug-in sensor offers superb false alarm immunity and the latest sensor technology
  • Broad ranges for operating temperature (-4°F to 158°F) and humidity (0% to 95% non-condensing)
  • Patented sampling tube installs from front or back of the detector with no tools required
  • Increased wiring space with a newly added conduit knockout
  • One easy-access Test/Reset button and improved LED status
  • System Sensor's patented interconnect feature for multi-fan shutdown
  • New high contrast terminal designations
  • Built-in short circuit protection from operator wiring errors
  • Field selectable settings for configuring the detector
  • Two DPDT Form-C relay contacts
  • 24 VAC/DC or 120VAC

Specifications

Weight2.35 Pounds (lbs)
Width2.4 Inches (In)
Height14.2 Inches (In)
Country of OriginMEX
Length4.9 Inches (In)
Air Velocity (FPM)100 to 4000 ft/min
BrandTotaline
Comments/Notes4-WIRE PHOTO-ELECT
CSA ListingYes
Operating Humidity0% to 95% non-condensing
Operating Temperature Range(-4F to 158F)
Overall Length4.9
Prop 65No
Storage Temperature22°F to 158°F